THERMATEC Products - heat pumps, hydraulic cabinets, DHW and buffer tanks

SMART SOLUTIONSHeat Pumps PLUS S LINE - NEW 2023smart solutions

Inverter heat pumps THERMATEC PLUS S LINE combine all modern elements. Eco-friendly refrigerant R290, full DC inverter, quiet technology, modern design, these are just some of the advantages of these powerful heat pumps.

Check out our range of heat pumps and choose the model that suits your building.

TECHNOLOGY & DESIGNSelected advantages of our devices:TECHNOLOGY & DESIGN

Smart Grid Function
01. Smart Grid Function

Thanks to this function, it is possible to configure the heat pump settings in such a way as to maximize the use of excess electricity from the photovoltaic installation. An additional advantage is the option to take advantage of cheaper tariffs offered by energy suppliers.

Kontrola stref grzewczych
02. Control of heating zones

The ability to control two independent heating zones in the building, thanks to full control over circulation pumps and smooth regulation of the mixing valve.

Heating Curve Function
03. Heating curve function

The ability to set eight heating curves based on the external ambient temperature with the possibility of modifying the heating curve.

Integrated Bracket with Heat Pump
04. Integrated bracket with the heat pump

The system of integrating the bracket with the heat pump excludes the need to purchase separate mounting systems. It also allows for the use of a full enclosure, which creates a modern design.

Smart Touch Display
05. Smart Touch display

The Smart Touch intelligent touch controller allows you to monitor and intuitively set the parameters of your heat pump’s operation in real-time. The high-quality 5-inch display with high resolution makes setting adjustments very easy.

Unique Enclosure Design
06. Unique enclosure design

Our engineers have designed a unique housing construction that limits the unit’s frosting process while making the heat pump defrosting process easier. This ensures the efficient and economical operation of the unit.

High-quality components

Our device is equipped with high-quality components from renowned brands, such as:

  • HIGHLY HITACHI
  • GRUNDFOS
  • DANFOSS
Highest quality of craftsmanship

Heat pump cascade

The software allows for connecting heat pumps in a cascade of up to eight devices of the same type. This design provides complete flexibility in building a system with the desired capacity.

Heat pump system up to 8 units in cascade

SG READY function

The SG READY function is one of the features that is built into all PLUS S LINE heat pumps. SG READY means that the pump is ready to operate in „Smart Grid” mode, which is an intelligent network.

Ready to operate in „Smart Grid” mode

Technical specificationComparison of PLUS S LINE heat pumps models:Technical Specification

  • TH-R290-S06-1P
  • TH-R290-S10-3P
  • TH-R290-S16-3P
Heat pump Thermatec TH-R290-S06-1P
Parameters Unit TH-R290-S06-1P
Power supply / 220–240V / 1N~ / 50Hz
Input power KW 6
Heating (A7/W35)
Heating capacity range kW 2.94 – 9.00
Input power kW 0.61 – 2.11
Input current A 2.80 – 9.25
COP kW/kW 4.27 – 4.82
Heating (A7/W55)
Heating capacity range kW 3.10 – 8.12
Input power kW 1.03 – 2.92
Input current A 4.57 – 12.79
COP kW/kW 2.78 – 3.01
Cooling (A35/W12)
Cooling capacity range kW 1.42 – 5.69
Input power kW 0.67 – 2.44
Input current A 3.06 – 10.27
SCOP average (THW at 35°C) kWh/kWh 4.80
SCOP average (THW at 55°C) kWh/kWh 3.67
Rated input power kW 3.50
Rated input current A 15
Refrigerant TYPE / CHARGE / GWP - / kg /- R290 / 0.55 / 3
CO2 equivalent TCO2eq 0.0017
Operation pressure (low side) MPa 0.8
Operation pressure (high side) MPa 3.0
Maximum allowable pressure MPa 3.2
Electrical shockproof Class I
Ingress protection IP IPX4
Maximum outlet water temperature °C 75
Operationg ambient temperature °C -25 ~ 45
Water piping connections cal G1
Rated water flow m³/h 1.0
Water pressure drop kPa 20
Water pressure (min. - max.) MPa 0.1 – 0.3
Sound pressure (1 m) dB(A) 44
Net dimensions (L x W x H) mm 1287 x 529 x 1054
Net weight kg 150
Bracket YES integrated

NOMINAL TEST CONDITIONS
Heating (A7/W35): Outdoor temperature 7°C/6°C (DB/WB) Water inlet/outlet 30°C/35°C
Heating (A7/W55): Outdoor temperature 7°C/6°C (DB/WB) Water inlet/outlet 47°C/55°C
Cooling (A35/W12): Outdoor temperature 35°C/24°C (DB/WB) Water inlet/outlet 12°C/7°C

Heat pump Thermatec TH-R290-S10-3P
Parameters Unit TH-R290-S10-3P
Power supply / 380–415V / 3N~ / 50Hz
Input power KW 10
Heating (A7/W35)
Heating capacity range kW 4.32 – 15.00
Input power kW 0.87 – 3.73
Input current A 1.78 – 6.04
COP kW/kW 4.02 – 4.97
Heating (A7/W55)
Heating capacity range kW 4.23 – 14.53
Input power kW 1.45 – 4.28
Input current A 2.84 – 6.78
COP kW/kW 2.92 – 3.39
Cooling (A35/W12)
Cooling capacity range kW 3.66 – 11.01
Input power kW 1.12 – 3.97
Input current A 1.97 – 6.30
SCOP average (THW at 35°C) kWh/kWh 4.70
SCOP average (THW at 55°C) kWh/kWh 3.62
Rated input power kW 5.85
Rated input current A 10
Refrigerant TYPE / CHARGE / GWP - / kg /- R290 / 1.05 / 3
CO2 Equivalent TCO2eq 0.0032
Operation pressure (low side) MPa 0.8
Operation pressure (high side) MPa 3.0
Maximum allowable pressure MPa 3.2
Electrical shockproof Class I
Ingress protection IP IPX4
Maximum outlet water temperature °C 75
Operationg ambient temperature °C -25 ~ 45
Water piping connections cal G1
Rated water flow m³/h 1.72
Water pressure drop kPa 20
Water pressure (min. - max.) MPa 0.1 - 0.3
Sound pressure (1 m) dB(A) 46
Net dimensions (L x W x H) mm 1387 x 549 x 1154
Net weight kg 170
Bracket YES integrated

NOMINAL TEST CONDITIONS
Heating (A7/W35): Outdoor temperature 7°C/6°C (DB/WB) Water inlet/outlet 30°C/35°C
Heating (A7/W55): Outdoor temperature 7°C/6°C (DB/WB) Water inlet/outlet 47°C/55°C
Cooling (A35/W12): Outdoor temperature 35°C/24°C (DB/WB) Water inlet/outlet 12°C/7°C

Heat pump Thermatec TH-R290-S16-3P
Parameters Unit TH-R290-S16-3P
Power supply / 380–415V / 3N~ / 50Hz
Input power KW 16
Heating (A7/W35)
Heating capacity range kW 7.25 – 21.70
Input power kW 1.50 – 5.88
Input current A 2.82- 9.16
COP kW/kW 3.69 - 4.83
Heating (A7/W55)
Heating capacity range kW 6.36 – 19.43
Input power kW 2.15 – 6.85
Input current A 3.71 – 10.60
COP kW/kW 2.84 - 2.96
Cooling (A35/W12)
Cooling capacity range kW 4.56 – 17.00
Input power kW 1.85 – 7.31
Input current A 2.99 – 11.26
SCOP average (THW at 35°C) kWh/kWh 4.72
SCOP average (THW at 55°C) kWh/kWh 3.65
Rated input power kW 10.50
Rated input current A 17
Refrigerant TYPE / CHARGE / GWP - / kg /- R290 / 1.4 / 3
CO2 Equivalent TCO2eq 0.0042
Operation pressure (low side) MPa 0.8
Operation pressure (high side) MPa 3.0
Maximum allowable pressure MPa 3.2
Electrical shockproof Class I
Ingress protection IP IPX4
Maximum outlet water temperature °C 75
Operationg ambient temperature °C -25 ~ 45
Water piping connections cal G1 ¼
Rated water flow m³/h 2.75
Water pressure drop kPa 55
Water pressure (min. - max.) MPa 0.1 - 0.3
Sound pressure (1 m) dB(A) 52
Net dimensions (L x W x H) mm 1287 x 599 x 1704
Net weight kg 265
Bracket YES integrated

NOMINAL TEST CONDITIONS
Heating (A7/W35): Outdoor temperature 7°C/6°C (DB/WB) Water inlet/outlet 30°C/35°C
Heating (A7/W55): Outdoor temperature 7°C/6°C (DB/WB) Water inlet/outlet 47°C/55°C
Cooling (A35/W12): Outdoor temperature 35°C/24°C (DB/WB) Water inlet/outlet 12°C/7°C